PVC Flexible Power Cable

PVC Flexible Power Cable

Construction

  • A. Tinned Copper Strand: 36 AWG
  • B. Strand Construction: See Below
  • C. Insulated with PVC, 80 C, 300 volts
    • 1. Wall thickness: see below
    • 2.Color: To be specified
    • 3. UL 1662
Part NumberAWG SizeStrand ConstructionNo. Of EndsCirc Mils.Min. Wall ThicknessNom. Overall O.D.

Nom. Carrying Capacity Amps

CW 3563-02187x10x366315750.0150.08212
CW 3563-01167x15x3610526250.0150.119
CW 3563-0147x24x3616842000.020.12830
CW 3563-2127x37x3625964750.020.14835
CW 3563-4107x59x36413103250.020.17550
CW 3563-687x95x36665166250.030.23370
CW 3563-877x119x36833208250.030.25380
CW 3563-1067x150x361050262500.030.27695
CW 3563-1247x7x34x361666416500.030.349125
CW 3563-1427x7x54x362646661500.030.422170
CW 3563-1617x7x68x363332833000.040.488195
CW 3563-181/07x7x86x3642141053500.040.538230
CW 3563-202/07x7x108x3652921323000.050.614265
CW 3563-223/019x7x51x3667831695750.060.679310
CW 3563-244/019x7x64x3685122128000.080.789360

PVC Flexible Power Cable

  • Construction
    • A. Tinned Copper Strand: 36 AWG
    • B. Strand Construction: See Below
    • C. Insulated with PVC, 105 C, 300 volts
  • 1. Wall thickness: see below
  • 2. Color: To be specified
  • 3. UL 10198, CSA Approved, VW-1 Rated
Part NumberAWG SizeStrand ConstructionNo. Of EndsCirc Mils.Min. Wall ThicknessNom. Overall O.D.Nom. Carrying Capacity Amps
CW 6254-02187×10/366315750.0150.08312
CW 6254-01167×15/3610526250.0150.09819
CW 6254-0147×24/3616842000.020.12630
CW 6254-2127×37/3625964750.020.14635
CW 6254-4107×59/36413103250.020.17350
CW 6254-687×95/3666516620.030.23570
CW 6254-877×119/36833208250.030.24980
CW 6254-1067×150/361050262500.030.27295
CW 6254-1247x7x34/361666416500.030.349125
CW 6254-1427x7x54/362646661500.030.422170
CW 6254-1617x7x68/363332833000.040.488195
CW 6254-181/07x7x86/3642141053500.040.538230
CW 6254-202/07x7x108/3652921323000.050.614265
CW 6254-223/019x7x51/3667831695750.060.679310
CW 6254-244/019x7x64/3685122128000.080.789360

PVC Flexible Power Cable Construction

  • A. Tinned Copper Strand: 36 AWG
  • B. Strand Construction: See Below
  • C. Insulated with PVC, 105 C, 600 volts
  • 1.Wall thickness: see below
  • 2. Color: To be specified
  • 3. UL 10070, CSA Approved
Part NumberAWG SizeStrand ConstructionNo. Of EndsCirc Mils.Min. Wall ThicknessNom. Overall O.D.Nom. Carrying Capacity Amps
CW 5361-02187x10x366315750.030.11612
CW 5361-01167x15x3610526250.030.13119
CW 5361-0147x24x3616842000.030.14830
CW 5361-2127x37x3625964750.030.16835
CW 5361-4107x59x36413103250.030.19550
CW 5361-687x95x3666516620.0450.26370
CW 5361-877x119x36833208250.060.31580
CW 5361-1067x150x361050262500.060.33895
CW 5361-1247x7x34x361666416500.060.415125
CW 5361-1427x7x54x362646661500.060.488170
CW 5361-1617x7x68x363332833000.080.576195
CW 5361-181/07x7x86x3642141053500.080.626230
CW 5361-202/07x7x108x3652921323000.080.68265
CW 5361-223/019x7x51x3667831695750.080.723310
CW 5361-244/019x7x64x3685122128000.080.789360
Jacket color to be specified. PVC Flexible Power Cable Construction